Description
Number of modules | 1 |
Standard packing | 12 |
Approvals | VDE |
Standards | IEC 60947-4-1, EN 60947-4-1, IEC 61095, EN 61095 |
Rated insulation voltage (Vac) | 400Vac |
Rated operational voltage (Vac) | 400Vac |
Switching-on capacity at 220-230Vac 1-phase (A) | 100 A |
Switching-off capacity at 220-230Vac 1-phase (A) | 80 A |
Fuse type GL for short-circuit protection (A) | 20 A |
Ohmic loss per contact at In (W) | 1.0 W |
Maximum switching frequency AC1/AC7A | 300/h |
Maximum switching frequency AC3/AC7B | 600/h |
Mechanical service life | 1.000.000 connections |
Electrical service life ac1 / ac7a | 150000 |
Electrical service life ac3 / ac7b | 150000 |
Screws | Pozidriv 1 |
Terminal capacity min | 1 x 1 mm² |
Magnet contr sys Control voltage range | 85 – 110%x Vnom |
Magnet contr sys Rated operating frequency (Hz) | 50 or 60Hz |
Magnet contr sys Operating temperature range (°C) | -25°C / +55°C |
Magnet contr sys Maximum pull-in coil power loss | 8.0 VA / 5.0 W |
Magnet contr sys Maximum holding coil power loss | 3.2 VA / 1.2 W |
Magnet contr sys Switching-on delay (ms) | 9 – 12 ms |
Magnet contr sys Switching-off delay (ms) | 10 – 12 ms |
Magnet contr sys Screws | Pozidriv 1 |
Terminal capacity max (mm²) | 1 x 10 mm² / 2 x 4 mm² |
Magnet contr sys Terminal capacity min (mm²) | 1 x 1 mm² |
Magnet contr sys Terminal capacity max (mm²) | 1 x 4 mm² or 2 x 2.5 mm² |
EAN13 | 5413656661283 |
Weight | 0.2 kg |